XH(A)E 49-A

Category: Brand:

Description

Standards:
Former code: XH(A)E 49, XH(A)E 49-A

Type coded acc, to HRN HD:

  • N2XS(FL)2Y,
  • NA2XS(FL)2Y,
  • EXeCeWB, EAXeCeWB

Type coded acc, to DIN VDE:

  • N2XS(FL)2Y,
  • NA2XS(FL)2Y

Standards and norms:

  • HRN HD 620 S2 Part 10C,
  • IEC 60 502-2
  • DINVDE 0276T 620

Nominal voltage: U₀/U=12/20 kV, 18/30 kV, 20.8/36 kV
Max. network voltage: Uₘ=24 kV, 36 kV, 42 kV
Test voltage: Uₜ=30 kV, 45 kV, 52 kV

 

 

Sizes and weights N2XS(FL)2Y, NA2XS(FL)2Y 12/20/24

 

Cross-section of Conductor & Electric Protection (n×mm²/mm²) Conductor Diameter (mm) Insulation Thickness (mm) Diameter over Insulation (mm) Sheath Thickness (mm) Approx. Cable Diameter (mm) Approx. Cable Weight Copper (kg/km) Approx. Cable Weight Aluminium (kg/km) Minimal Bending Radius (mm)
1×35/16 7.2 5.5 20.3 2.5 28 1100 900 420
1×50/16 8.3 5.5 21.4 2.5 29 1255 965 430
1×70/16 10.3 5.5 23.4 2.5 31 1510 1060 460
1×95/16 11.3 5.5 24.4 2.5 32 1765 1170 480
1×120/16 12.7 5.5 25.8 2.5 34 2010 1320 510
1×150/25 14.1 5.5 27.2 2.5 36 2320 1475 550
1×185/25 15.5 5.5 28.6 2.5 38 2630 1600 570
1×240/25 18.0 5.5 31.1 2.5 41 3300 1880 610
1×300/25 20.5 5.5 33.6 2.5 44 3830 2100 660
1×400/35 23.8 5.5 36.9 2.5 48 4985 2595 700
1×500/35 26.7 5.5 39.8 2.5 51 6080 2990 720