Description
| Designation: | Standard: |
| NA2XY | HD 603 S1 5G-2, IEC 60502-1, DIN VDE 0276-603 |
| XP00-A | MKS N.C3.230 |
Application:
For power supply in industrial plants, power station, for underground laying, in watter, in concrete, if no mechanical damage is to be expected.
Construction:
1 – Conductor: stranded aluminium wires (round and sector shaped), with or without signal/control copper conductor
2 – Insulation: XLPE DIX 3 correspond to HD 603-1.
3 – Filler: Epdm rubber or polyester tape
4 – Sheathing material: PVC compound DMV 6 to HD 603-1.
Technical data:
| Number of cores, nominal cross cectional area mm² |
Conductor shape | Maximum resistance of conductor at 20⁰C | Overall diameter (approx.) | Rated current-carrying capacity in earth | Rated current-carrying capacity in air | Total net weight (approx.) | Packing – drum |
| Number x mm² | Ω/km | mm | A | A | kg/km | m | |
| 1×16 | RM | 1.91 | 11.5 | – | – | 145 | 1000 /N⁰9 |
| 1×25 | RM | 1.20 | 12.8 | 177 | 136 | 196 | 1000 /N⁰9 |
| 1×35 | RM | 0.868 | 13.7 | 212 | 166 | 250 | 1000 /N⁰10 |
| 1×50 | RM | 0.641 | 15 | 252 | 205 | 290 | 1000 /N⁰10 |
| 1×70 | RM | 0.443 | 17 | 310 | 260 | 393 | 1000 /N⁰10 |
| 1×95 | RM | 0.320 | 19 | 372 | 321 | 510 | 1000 /N⁰12 |
| 1×120 | RM | 0.253 | 20.2 | 425 | 376 | 601 | 1000 /N⁰13 |
| 1×150 | RM | 0.206 | 22.1 | 476 | 431 | 712 | 1000 /N⁰13 |
| 1×185 | RM | 0.164 | 25 | 541 | 501 | 884 | 1000 /N⁰14 |
| 1×240 | RM | 0.125 | 28 | 631 | 600 | 1100 | 1000 /N⁰15 |
| 1×300 | RM | 0.100 | 30.4 | 716 | 696 | 1440 | 1000 /N⁰16 |
| 1×400 | RM | 0.0778 | 34 | 825 | 821 | 1812 | 500 /N⁰14 |
| 4×16 | RM | 1.91 | 21 | – | – | 638 | 500 /N⁰10 |
| 4×25 | RM | 1.20 | 26 | 112 | 102 | 923 | 500 /N⁰12 |
| 4×35 | RM | 0.868 | 28 | 135 | 126 | 745 | 500 /N⁰13 |
| 4×35 | SM | 0.868 | 26 | 135 | 126 | 710 | 500 /N⁰12 |
| 4×50 | SM | 0.641 | 29 | 158 | 149 | 903 | 500 /N⁰13 |
| 4×70 | SM | 0.443 | 33 | 196 | 191 | 1207 | 500 /N⁰15 |
| 4×95 | SM | 0.320 | 38 | 234 | 234 | 1587 | 500 /N⁰15 |
| 4×120 | SM | 0.253 | 42 | 268 | 273 | 1938 | 500 /N⁰16 |
| 4×150 | SM | 0.206 | 46 | 300 | 311 | 2354 | 500 /N⁰18 |
| 4×185 | SM | 0.164 | 51 | 342 | 360 | 2998 | 500 /N⁰20 |
| 4×240 | SM | 0.125 | 56 | 398 | 427 | 3745 | 500 /N⁰20 |
| 4×16+1.5 | RM+RE | 1.91/12.1 | 22 | – | – | 650 | 500 /N⁰10 |
| 4×25+1.5 | RM+RE | 1.20/12.1 | 21 | 112 | 102 | 940 | 500 /N⁰12 |
| 4×35+1.5 | RM+RE | 0.868/12.1 | 26 | 135 | 126 | 760 | 500 /N⁰13 |
| 4×35+1.5 | SM+RE | 0.868/12.1 | 28 | 135 | 126 | 732 | 500 /N⁰12 |
| 4×50+1.5 | SM+RE | 0.641/12.1 | 26 | 158 | 149 | 920 | 500 /N⁰13 |
| 4×70+1.5 | SM+RE | 0.443/12.1 | 29 | 196 | 191 | 1220 | 500 /N⁰15 |
| 4×95+1.5 | SM+RE | 0.320/12.1 | 33 | 234 | 234 | 1603 | 500 /N⁰15 |
| 4×120+1.5 | SM+RE | 0.253/12.1 | 38 | 268 | 273 | 1954 | 500 /N⁰16 |
| 4×150+1.5 | SM+RE | 0.206/12.1 | 42 | 300 | 311 | 2371 | 500 /N⁰18 |
| 4×185+1.5 | SM+RE | 0.164/12.1 | 46 | 342 | 360 | 3014 | 500 /N⁰20 |
| 4×240+1.5 | SM+RE | 0.125/12.1 | 51 | 398 | 427 | 3763 | 500 /N⁰20 |
| Nominal voltage | 0.6/1 kV |
| Test voltage | 4 kV |
| Highest operating temperature | +90⁰C |
| Short circuit temperature (5s) | 250⁰C |
| Minimum banding radius | 15x cable diameter |
| Colour of jacket | Black |
RM – multiwire round stranded conductor
SM – multiwire sector stranded conductor
RE – solid round conductor