NA2XS(F)2Y, XLPE 6/10 kV

Category: Brand:

Description

CONSTRUCTION:
1 Aluminum Conductor Compacted – Class 2
2 Inner Semi Conductive Layer
3 XLPE Insulation
4 Outer Semi Conductive Layer
5 Semi Conductive Tape
6 Copper Wire and Tape Screen
7 Water Blocking Tape
8 PE Sheath

 

Code (N)A2XS(F)2Y
Standartlar IEC 60502-2

APPLICATION:
This design of cable is used in underground or cable ducts for urban and
industrial areas to supply electrical energy.The design will become
capable to operate under wet conditions with additional applications.

Voltage Level:
Rated Coltage: Uo/U=6/10 kV

Technical Data:
Maximum operation temperature: 90 oC
Short circuit temperature Max. : 250 oC

 

Nominal Cross Section Insulation Thickness (mm) Overall Diameter approx. (mm) Net Weight approx. (kg/km) Conductor Resistance at 20 °C Max. (Ω/km) Operating Capacity Approx. (μF/km) Current Carrying Capacity – Earth (A) Current Carrying Capacity – Underground (A)
1×50/16 3.4 26.0 595 0.641 0.240 190 168
1×70/16 3.4 27.0 685 0.443 0.279 231 205
1×95/16 3.4 29.0 790 0.320 0.311 278 244
1×120/16 3.4 30.0 890 0.253 0.338 315 280
1×150/25 3.4 31.5 1,080 0.206 0.370 342 312
1×185/25 3.4 33.0 1,220 0.164 0.410 388 355
1×240/25 3.4 36.0 1,410 0.125 0.455 450 411
1×300/25 3.4 38.0 1,610 0.100 0.505 500 459
1×400/35 3.4 41.5 2,030 0.0778 0.565 554 530
1×500/35 3.4 45.0 2,400 0.0605 0.625 619 592
1×630/35 3.4 49.0 2,850 0.0469 0.690 710 678