Standards:
Former code: XHE 48/0, XHE 48/0-Ay
Standards and norms: IEC 60502-2
Nominal voltage: U₀/U=12/20 kV
Max. network voltage: Uₘ=24 kV
Test voltage: Uₜ=42 kV
Technical characteristics:
CONSTRUCTION DESCRIPTION
- Conductor: copper or aluminium rope, compacted
- Conductor screen: semi-conductive layer over conductor
- Insulation: XLPE
- Insulation screen: semi-conductive layer over insulation
- Electric protection/screen: of copper tape
- External sheath: PE-HD
| Cross-section of Conductor and Electric Protection (nxmm²/mm²) | Conductor Diameter (mm) | Insulation Thickness (mm) | Diameter over Insulation (mm) | Sheath Thickness (mm) | Cable Diameter approx. (mm) | Cable Weight approx. (kg/km) – Aluminium | Minimal Bending Radius (mm) |
| 3×70/16 | 10.1 | 5.5 | 23.3 | 2.8 | 57.5 | 2388 | 870 |
| 3×95/25 | 12.0 | 5.5 | 25.1 | 2.9 | 61.5 | 2800 | 930 |