NA2XS(F)2Y, XLPE 20,3/35 kV

Category: Brand:

Description

CONSTRUCTION:
1 Aluminum Conductor Compacted – Class 2
2 Inner Semi Conductive Layer
3 XLPE Insulation
4 Outer Semi Conductive Layer
5 Semi Conductive Swelling Tape
6 Copper Wire and Tape Screen
7 Water Blocking Tape
8 PE Sheath

 

Code (N)A2XS(F)2Y
Standartlar IEC 60502-2

 

APPLICATION:
This design of cable is used in underground or cable ducts for urban and
industrial areas to supply electrical energy.The design will become
capable to operate under wet conditions with additional applications.

 

Voltage Level:
Rated Coltage: Uo/U=20,3/35 kV

Technical Data:
Maximum operation temperature: 90 oC
Short circuit temperature Max. : 250 oC

 

Nominal Cross Section Insulation Thickness (mm) Overall Diameter approx. (mm) Net Weight approx. (kg/km) Conductor Resistance at 20°C Max. (Ω/km) Current Carrying Capacity – Earth (A) Current Carrying Capacity – Underground (A)
1×50/16 9 36.0 1140 0.641 192 171
1×70/16 9 38.0 1260 0.443 235 210
1×95/16 9 41.0 1440 0.320 280 247
1×120/16 9 41.0 1600 0.253 319 286
1×150/25 9 43.0 1750 0.206 352 321
1×185/25 9 45.0 2010 0.164 396 361
1×240/25 9 47.0 2160 0.125 456 423
1×300/25 9 49.0 2510 0.100 512 478
1×400/35 9 52.0 2820 0.0778 561 534
1×500/35 9 55.5 3000 0.0605 630 613
1×630/35 9 60.0 3720 0.0469 720 691